Measurement of the concentration and size of aerosol particles and identification of the sources in orthopedic surgeries

Carregando...
Imagem de Miniatura
Citações na Scopus
7
Tipo de produção
article
Data de publicação
2012
Título da Revista
ISSN da Revista
Título do Volume
Editora
TAYLOR & FRANCIS INC
Autores
PEREIRA, Marcelo Luiz
VILAIN, Rogerio
TRIBESS, Arlindo
Citação
HVAC&R RESEARCH, v.18, n.4, p.588-601, 2012
Projetos de Pesquisa
Unidades Organizacionais
Fascículo
Resumo
In this study, the measurement of the concentration and size of particles and the identification of their sources were carried out at five orthopedic surgeries. The aerosol concentration and particle size distribution, ranging from 0.3 mu m 10 mu m, were measured and related to the type of indoor activity. The handling of surgical linen and gowns, handling of the patient, use of electrosurgical apparatus, use of a bone saw, handling of equipment, and cleaning of the room were identified as the most important sources of particles, with each of these activities posing different risks to the health of the patients and workers. The results showed that most of the particles were above 0.5 mu m and that there was a strong correlation among all particles of sizes above 1 mu m. Particles with diameters in the range of 0.3 mu m-0.5 mu m had a good correlation only with particles in the ranges of 0.5 mu m-1.0 mu m and 1.0 mu m-3.0 mu m in three of the surgeries analyzed. Findings led to the conclusion that most of the events responsible for generating aerosol particles in an orthopedic surgery room are brief, intermittent, and highly variable, thus requiring the use of specific instrumentation for their continuous identification and characterization.
Palavras-chave
Referências
  1. Alp E, 2006, J HOSP INFECT, V62, P1, DOI 10.1016/j.jhin.2005.01.014
  2. Andersen Bjorg Marit, 1998, Tidsskrift for den Norske Laegeforening, V118, P3148
  3. Beggs C.B., 2003, INDOOR BUILT ENVIRON, V12, P1
  4. Bruske-Hohlfeld I., 2008, J OCCUPATIONAL MED T, V3, P1
  5. Clark R.P., 1973, AIRBORNE TRANSMISSIO
  6. Clark RP, 2009, J R SOC INTERFACE, V6, pS767, DOI 10.1098/rsif.2009.0236.focus
  7. CLARK RP, 1985, J HYG-CAMBRIDGE, V95, P325
  8. Dharan S, 2002, J HOSP INFECT, V51, P79, DOI 10.1053/jhin.2002.1217
  9. HAMBRAEUS A, 1978, J HYG-CAMBRIDGE, V80, P169
  10. KLUYTMANS JAJW, 1995, J INFECT DIS, V171, P216
  11. Landrin A, 2005, J HOSP INFECT, V61, P27, DOI 10.1016/j.jhin.2005.03.002
  12. Liu Y., 2002, P ROOM VENT 2002 8 I
  13. Morawska L, 1998, INDOOR AIR, V8, P285, DOI 10.1111/j.1600-0668.1998.00009.x
  14. Nogler M, 2001, EUR SPINE J, V10, P274, DOI 10.1007/s005860100310
  15. NRHBWP (Newcastle Regional Hospital BoardWorking Party), 1962, J HYGIENE, V60, P85
  16. Pereira M.L., 2008, THESIS U SAO PAULO S
  17. Roberts K, 2006, INDOOR BUILT ENVIRON, V15, P35, DOI 10.1177/1420326X06062562
  18. Scaltriti S, 2007, J HOSP INFECT, V66, P320, DOI 10.1016/j.jhin.2007.05.019
  19. SEAL DV, 1990, J APPL BACTERIOL, V68, P225, DOI 10.1111/j.1365-2672.1990.tb02568.x
  20. Thatcher TL, 2002, ATMOS ENVIRON, V36, P1811, DOI 10.1016/S1352-2310(02)00157-7
  21. WENIG BL, 1993, LASER SURG MED, V13, P242, DOI 10.1002/lsm.1900130213
  22. YEH HC, 1995, AEROSOL SCI TECH, V22, P151, DOI 10.1080/02786829408959736